FPLR SHIELDED FIRE ALARM CABLE E- SERIES

The UL listed FPLR shielded fire alarm E-series cable from Norden is suitable to be use in a vertical runs in signaling & fire alarm system. It works in high temperature levels. This cable is constructed with FR-PVC insulation and outer jacket with aluminum foil shielding that meets UL 1666 specifications. This cable complies with VW - 1 Flame Test requirements in ANSI/UL 1581.Tested as per ANSI/UL 1666 for flame propagation height of electrical and optical - Fibre Cables Installed Vertically in Shafts.

The UL listed FPLR shielded fire alarm E-series cable from Norden is suitable to be use in a vertical runs in signaling & fire alarm system. It works in high temperature levels. This cable is constructed with FR-PVC insulation and outer jacket with aluminum foil shielding that meets UL 1666 specifications. This cable complies with VW - 1 Flame Test requirements in ANSI/UL 1581.Tested as per ANSI/UL 1666 for flame propagation height of electrical and optical - Fibre Cables Installed Vertically in Shafts.

Standard

ANSI / UL 1424, Cables for Power - Limited Fire - Alarm Circuits

CABLE CONSTRUCTION


SECTION VIEW


ELECTRICAL & MECHANICAL CHARACTERISTICS

PropertiesValue
14AWG 
16AWG 

Max. Conductor Resistant @ 20ºC

8.45 Ω/km

13.5 Ω/km

Min. Insulation Resistant @ 15.6°C

100Ω/kft

Operating Voltage

300/500 V

Breakdown Test

2500 V

Temperature Range 

-35°C to +105°C

PHYSICAL INFORMATION

No. of Cores x
Conductor Size

Conductor diameter mm (±0.005) 
Insulation diameter mm (±0.1) 
Jacket Thicknes mm (±0.01)
Jacket diameter, mm (±0.3) 

2C x 14 AWG

1.63

2.7
0.58
6.8 

2C x 16 AWG

1.29

2.2
0.58
5.8
Part NumberDescription

5E-1502XY

2Core x 16 AWG FPLR Shielded Fire Alarm Cable E-Series

5E-2502XY

2Core x 14 AWG FPLR Shielded Fire Alarm Cable E-Series

X (Colour code) > RD: Red

Y (Packing length) > 1:100mtr, 2: 500mtr