2 Core 14 AWG Shielded Power Limited Fire Protective Signal Cable

2 Core 14 AWG Shielded Power Limited Fire Protective Signal Cable

The shielded power limited fire protective signal cable from Norden is suitable to be used for installation in signaling & fire alarm system. It works in high temperature level. This cable is constructed with PVC Insulation, 100 % Aluminium Foil – Polyester Tape Shield with PVC fire protective outer jacket.

The shielded power limited fire protective signal cable from Norden is suitable to be used for installation in signaling & fire alarm system. It works in high temperature level. This cable is constructed with PVC Insulation, 100 % Aluminium Foil – Polyester Tape Shield with PVC fire protective outer jacket.

CABLE CONSTRUCTION

Conductor

Solid Bare Copper

Outer Jacket

PVC (UL 1666 Riser)

Shielding

Aluminium Foil - Polyester Tape

Insulation

PVC

Jacket Colour

Red

Foil Coverage

100%

Insulation Colour

2 Core: Red/Black

Standard Packing Mode

305 mtr / Plywood Reel

Drain Wire

Tinned Copper

SECTION VIEW

PHYSICAL CHARACTERISTICS

Characteristic Value

No. of Conductor

2

Conductor Size

14AWG

Insulation Diameter

2.80 mm

Drain Wire Size

0.25 x 26

Jacket Thickness

1.10 mm

Jacket Diameter

7.80 mm

Max. Recommended Pulling Tension

255 N

Min. Bending Radius Minor Axis

78 mm

Operating Temperature

-20°C to +75°C

ELECTRICAL CHARACTERISTICS

Characteristic Value Unit

Nom. Conductor DCR

?/km

8.5

Dielectric Strength between Pairs

KV/5min

1.5

Max. Operating Voltage UL

V/min

300

MECHANICAL CHARACTERISTICS

Characteristic Value

Test Material

PVC

Before Tensile Strength (Mpa)

?13.8

Aging Elongation (%)

?100

After Tensile Strength (Mpa)

?85

Aging Elongation (% of unaged)

?50

Cold Bend (-20±°C x 4 hrs)

No Crack

Standard & Environmental

UL Style 2464

Part Number Description

75-1202141

2 CORE 14AWG Shielded Power Limited Fire Protective Signal Cable