300-600kVA DOUBLE CONVERSION TRANSFORMER-BASED UPS

Ultra Power Series is a transformer-based UPS of Cellnor, both input and output are 3 phases.The output power factor is 0.9. These ups can work in parallel and expand its power capacity.This series UPS is highly reliable and have good impact resistance, it can supply safe and reliable protection for the load

Ultra Power Series is a transformer-based UPS of Cellnor, both input and output are 3 phases. The output power factor is 0.9. These ups can work in parallel and expand its power capacity.This series UPS is highly reliable and have good impact resistance, it can supply safe and reliable protection for the load

GENERAL FEATURES

    • Online Double Conversion
    • Full DSP Control
    • High Power Factor
    • Wide input adaptability
    • Optimized battery management
    • N+X parallel redundancy
    • Strong overload capability
    • Multi-protection
    • 6 Pulse and 12 Pulse Recti
    • EPO function 


    Specification

    ModelCN933300U 
    CN433400TU 
    CN433500TU 
    CN433600TU

    Capacity

    kVA

    300kVA

    400kVA
    500kVA
    600kVA

    Watts

    270kW

    360kW
    450kW
    540kW 

    Input

    Normal Voltage380/400/415Vac (3Ph+N+PE) (-25% +20%)
    Harmonic distortion(THDi) 
    <3%(100% linear load) 
    Operating frequency range
    50/60Hz (±5Hz) 
    Power factor
    0.98 (with filter)
    Bypass voltage range

    Upper limit:+20%(+10%,+15%,+20% adjustable)

    Lower limit:-40%(-10%,-20%,-30%,-40% adjustable)

    Bypass Frequency range
    ±10%(±2.5%,±5%,±10%,±20% adjustable)

    Output

    Rated voltage380/400/415Vac (3Ph+N+PE)
    Power factor
    0.9
    Voltage regulation
    ±1%
    Frequency   
    50/60(±0.1)Hz
    Crest factor
    3:1
    Harmonic distortion (THDv)
    ≤2% with linear load
    Efficiency
    >93%                                                                           >93.5%
    Output Waveform
    Pure Sine Wave

    Battery

    Battery voltage384Vdc (30/32/34pcs)                                               480Vdc (40pcs)

    System Features

    Transfer timeMains to battery:0ms
    Overload  
    110%60min, 125%10min, 150%1min
    LED Display
    Input, Inverter, Bypass, Battery, Output, Status 
    LCD Display 
    I/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record, settings
    Communication 
    USB, RS232, RS485, Parallel port,dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional)

    Environment

    Operating temperature0~40°C
    Storage temperature
    -25~55°C
    Humidity range
    0~95% (Non-condensing)
    Altitude
    <1500m
    Noise level
    <70dB

    Physical

    Dimension WxDxH(mm)1400x1000x1900 (6P)/1640x1000x1900(12P)      2580x1000x1900            2800x1040x1900
    Net Weight (kg)
    1560/2395 1640/25103510
    4500

    Standards

    SafetyIEC/EN62040-1,IEC/EN60950-1
    EMC

    IEC/EN 62040-2;IEC 61000-2-2;IEC 61000-4-2;IEC 61000-4-3;IEC 61000-4-4

    IEC 61000-4-5;IEC 61000-4-6;IEC 61000-4-8;IEC 61000-4-11

    Performance
    IEC62040-3


                                                                          

    Part NumberDescription
    CN933300U
    300kVA Double Conversion Transformer-Based UPS Input/Output Three-Phase
    CN433400TU
    400kVA Double Conversion Transformer-Based UPS Input/Output Three-Phase
    CN433500TU
    500kVA Double Conversion Transformer-Based UPS Input/Output Three-Phase
    CN433600TU
    600kVA Double Conversion Transformer-Based UPS Input/Output Three-Phase