10-30KVA DOUBLE CONVERSION TRANSFORMER-BASED UPS

Ultra Power Series is a transformer-based UPS of Cellnor, both input and output are 3 phases. The output power factor is 0.9. These ups can work in parallel and expand its power capacity. This series UPS is highly reliable and have good impact resistance, it can supply safe and reliable protection for the load.

Ultra Power Series is a transformer-based UPS of Cellnor, both input and output are 3 phases. The output power factor is 0.9. These ups can work in parallel and expand its power capacity. This series UPS is highly reliable and have good impact resistance, it can supply safe and reliable protection for the load. 

GENERAL FEATURES

    • Online Double Conversion
    • Full DSP Control
    • High Power Factor
    • Wide input adaptability
    • Optimized battery management
    • N+X parallel redundancy
    • Strong overload capability
    • Multi-protection
    • Generator mode
    • EPO function 


    Specification

    ModelCN43310TU 
    CN43320TU 
    CN43330TU 

    Capacity

    kVA

    10kVA

    20kVA
    30kVA

    Watts

    9kW

    18kW
    27kW

    Input

    Normal Voltage380/400/415Vac (3Ph+N+PE) (-25% +20%)
    Harmonic distortion(THDi) 
    <3%(100% linear load) 
    Operating frequency range
    50/60Hz (±5Hz) 
    Power factor
    0.98 (with filter)
    Bypass voltage range

    Upper limit:+20%(+10%,+15%,+20% adjustable)

    Lower limit:-40%(-10%,-20%,-30%,-40% adjustable)

    Bypass Frequency range
    ±10%(±2.5%,±5%,±10%,±20% adjustable)

    Output

    Rated voltage380/400/415Vac (3Ph+N+PE)
    Power factor
    0.9
    Voltage regulation
    ±1%
    Frequency   
    50/60(±0.1)Hz
    Crest factor
    3:1
    Harmonic distortion (THDv)
    ≤2% with linear load
    Efficiency
    >88%                                                                           >89%
    Output Waveform
    Pure Sine Wave

    Battery

    Battery voltage384Vdc (30/32pcs)

    System Features

    Transfer timeMains to battery:0ms; Mains to bypass:0ms
    Overload  
    ≤110%: Overload 60min, ≤150%: Overload 1min, >150% turn to bypass mode immediately
    LED Display
    Input, Inverter, Bypass, Battery, Output, Status 
    LCD Display 
    I/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record, settings
    Communication 
    USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional)

    Environment

    Operating temperature0~40°C
    Storage temperature
    -25~55°C
    Humidity range
    0~95% (Non-condensing)
    Altitude
    <1500m
    Noise level
    <70dB

    Physical

    Dimension WxDxH(mm)570x800x1195
    Net Weight (kg)
    217273316

    Standards

    SafetyIEC/EN62040-1,IEC/EN60950-1
    EMC

    IEC/EN 62040-2;IEC 61000-2-2;IEC 61000-4-2;IEC 61000-4-3;IEC 61000-4-4 IEC 61000-4-5;IEC 61000-4-6;IEC 61000-4-8;IEC 61000-4-11 2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

    Performance
    IEC62040-3


                                                                          

    Part NumberDescription
    CN43310TU
    10kVA Double Conversion Transformer-Based UPS 
    CN43320TU
    20kVA Double Conversion Transformer-Based UPS
    CN43330TU 
    30kVA Double Conversion Transformer-Based UPS