10kVA Online Transformer-less UPS

MAXPOWER PRO is a small to medium power transformer-less UPS of CellNor. This UPS has a high output power factor at 0.9PF and a wide input voltage range: 110~286Vac. The CN6010MPI, CN6010MPE model support economic (ECO) operation mode.

MAXPOWER PRO is a small to medium power transformer-less UPS of CellNor. This UPS has a high output power factor at 0.9PF and a wide input voltage range: 110~286Vac. The CN6010MPI, CN6010MPE model support economic (ECO) operation mode. 

 GENERAL FEATURES

  • N+X parallel redundancy, support maximum 4 unit in parallel
  • Online double conversion with full digital control
  • Optimization battery group, the quantity of battery: 16/18/20Pcs (Settable)
  • Selectable output voltage:220/230/240Vac
  • Wide input voltage range:110~286Vac
  • Wide input frequency range
  • Maximum charging current up to 10A
  • ECO mode operation for energy saving
  • Multiple communication interface:RS232 (USB/Dry contact/SNMP card optional)
  • Self-testing when UPS start-up
  • Generator compatible
  • Cold start

SPECIFICATIONS


ModelCN6010MPI, CN6010MPE

Capacity

VA

10000

Watts

9000

Input

Normal Voltage

220/230/240Vac(L+N+PE) 

Operating Voltage Range

110~286Vac

Operating Frequency Range

40~70Hz (50/60Hz Auto-Sensing)

Power Factor

≥0.99 

Bypass voltage range

Max.voltage:230~264Vac

Min.voltage:176~220Vac

ECO range

Same as the bypass

Harmonic distortion (THDi)

≤5%(100% linear load)

Generator input

Support

Output

Output voltage

220/230/240Vac

Power factor

0.9

Voltage Regulation

±1%

Frequency

Line mode

±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)

Bat. mode

50/60(±0.1)Hz

Crest Factor

3:1

Harmonic Distortion (THDv)

≤2% with linear load, ≤5% with non-linear load

Efficiency

>93.5%

Battery

Battery voltage

(Standard unit 240Vdc) 192/216/240Vdc (Adjustable) with Neutral

Capacity (Standard unit)

9Ah/12V (7Ah/12V optional)

Typical recharging time

6~8 hours (to 90% of full capacity)

Charging current

1A(Standard unit); Long run unit Max.current 10A(charging current can be set according to battery capacity installed)

System
Features

Transfer time

Mains to battery:0ms; Mains to bypass:0ms

Overload

Line mode

Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately

Bypass mode

63A(Breaker)

Short circuit

Hold whole system

Overheat

Line mode: Turn to bypass; Backup mode: shut down UPS immediately

Battery low

Alarm and switch off

Self-diagnostics

Upon power on and software control

Battery

Advanced battery management

Audible & Visual alarms

Line failure, Battery under voltage, Overload, System fault

LED & LCD display

Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault

LCD display

Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time

Communication interface

RS232, USB,SNMP card(optional), Parallel card(optional), Relay card (optional)

Environment

Operating temperature

0~40°C 

Storage temperature

-25~55°C

Humidity range

0~95% (Non-condensing)

Altitude

<1500m

Noise level

<55dB 

Physical

Dimension

 I:191 x 460 x 720                  E:191 x 460 x 337

Weight

71/14

Standards

Safety

IEC/EN62040-1,IEC/EN62477-1

EMC

IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

 

 EXTERNAL BATTERY PACK


MODELCNBN10120CT
BATTERY SYSTEM

Battery type

VRLA (Lead acid maintenance free battery)

Typical battery recharging time 

6~8 hours (to 90% of full capacity) 

Typical battery life
3~5 years, depend on discharging cycle and ambient temperature
System voltage 
240Vdc
Battery quantity
2*±10 Pcs
Capacity
7Ah/9Ah (12V)
Backup time @ 50% load
43 minutes
Backup time @ 100% load 
15 minutes
PHYSICAL
Dimension W x D x H (mm) 
250 x 597 x 616
Net weight (kg)
122/134
ENVIRONMENT

Safety 
CE
Operating environment
0°C~40°C
Relative humidity 
0~95% (Non condensing) 
Noise level 
<40dB at 1 Meter
                                   
Part NumberDescription

CN6010MPI

10kVA Medium Power Transformerless UPS (internal battery)

CN6010MPE

10kVA Medium Power Transformerless UPS (external battery)
CNBN10120CT
120 VDC Battery Pack