Ultra Power Series is a transformer-based UPS of Cellnor, both input and output are 3 phases. The output power factor is 0.9. These ups can work in parallel and expand its power capacity. This series UPS is highly reliable and have good impact resistance, it can supply safe and reliable protection for the load
Ultra Power Series is a transformer-based UPS of Cellnor, both input and output are 3 phases. The
output power factor is 0.9. These ups can work in parallel and expand its power capacity. This series UPS
is highly reliable and have good impact resistance, it can supply safe and reliable protection for the
load
Model | CN433100TU | CN433120TU | CN433160TU | CN433200TU | |
Capacity | kVA | 100kVA | 120kVA | 160kVA | 200kVA |
Watts | 90kW | 108kW | 144kW | 180kW | |
Input | Normal Voltage | 380/400/415Vac (3Ph+N+PE) (-25% +20%) | |||
Harmonic distortion(THDi) | <3%(100% linear load) | ||||
Operating frequency range | 50/60Hz (±5Hz) | ||||
Power factor | 0.98 (with filter) | ||||
Bypass voltage range | Upper limit:+20%(+10%,+15%,+20% adjustable) Lower limit:-40%(-10%,-20%,-30%,-40% adjustable) | ||||
Bypass Frequency range | ±10%(±2.5%,±5%,±10%,±20% adjustable) | ||||
Output | Rated voltage | 380/400/415Vac (3Ph+N+PE) | |||
Power factor | 0.9 | ||||
Voltage regulation | ±1% | ||||
Frequency | 50/60(±0.1)Hz | ||||
Crest factor | 3:1 | ||||
Harmonic distortion (THDv) | ≤2% with linear load | ||||
Efficiency | >92% >92.5%
| ||||
Output Waveform | Pure SineWave | ||||
Battery | Battery voltage | 384Vdc (30/32/34pcs)
| |||
System Features | Transfer time | Mains to battery:0ms;
| |||
Overload | 110%60min, 125%10min, 150%1min | ||||
LED Display | Input, Inverter, Bypass, Battery, Output, Status | ||||
LCD Display | I/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage,
UPS status, history record, settings | ||||
Communication | USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional) | ||||
Environment | Operating temperature | 0~40°C | |||
Storage temperature | -25~55°C | ||||
Humidity range | 0~95% (Non-condensing)
| ||||
Altitude | <1500m | ||||
Noise level | <65dB | ||||
Physical | Dimension WxDxH(mm) | 1160x805x1600 (6P)/1520x830x1600 (12P) 1200x800x1600 (6P)/1400x1000x1900 (12P)
| |||
Net Weight (kg) | 800/1100 | 903/1250 | 980/1645 | 1030/1715 | |
Standards | Safety | IEC/EN62040-1,IEC/EN60950-1 | |||
EMC | IEC/EN 62040-2;IEC 61000-2-2;IEC 61000-4-2;IEC 61000-4-3;IEC 61000-4-4 IEC 61000-4-5;IEC 61000-4-6;IEC 61000-4-8;IEC 61000-4-11
| ||||
Performance | IEC62040-3 |
Part Number | Description | ||
CN433100TU | 100kVA Double Conversion Transformer-Based UPS Input/Output Three-Phase | ||
CN433120TU | 120kVA Double Conversion Transformer-Based UPS Input/Output Three-Phase | ||
CN433160TU | 160kVA Double Conversion Transformer-Based UPS Input/Output Three-Phase | ||
CN433200TU | 200kVA Double Conversion Transformer-Based UPS Input/Output Three-Phase |